Figure 6. UPS Battery Switchgear cabling diagram
1
External Battery Switchgear 5 String breaker n
2 Breaker 6 Battery cabinet 1
3 UPS 7 Battery cabinet n
4 String breaker 1
3.7 Basic system configurations
UPS power rating
The maximum attainable UPS system power rating is determined by the size of
the UPS cabinet frame. The number of UPM power modules determines the
nominal power rating of the UPS. If upgradeability is required, the system static
bypass should be chosen according to the future maximum load rating, and the
number of UPMs is chosen according to the capacity requirements on day one.
The following UPS configurations with different static bypass sizes and number
of UPMs are possible:
Table 2: UPS configurations
Description
System
power
[kW]
Power
modules
[kW]
Static
switch
[kW]
Internal battery
93PM-30(50) 30 1x30 50 Yes/No
93PM-40(50) 40 1x40 50 Yes/No
93PM-50(50) 50 1x50 50 Yes/No
93PM-60(60) 54 kW /
60 kVA
1x60 kVA 54 kW / 60
kVA
Yes/No
Eaton 93PM UPS 30–200 kVA User's and installation guide
©
Eaton Corporation plc 2017. All rights reserved. Revision: 005 Document ID: P-164000249 32 (126)