Description
System
power
[kW]
Power
modules
[kW]
Static
switch
[kW]
Internal battery
93PM 40(100) 40 1x40 100 No
93PM 40(150) 40 1x40 150 No
93PM 40(200) 40 1x40 200 No
93PM 40+40(100) 40 2x40 100 No
93PM-50(100) 50 1x50 100 No
93PM 50(150) 50 1x50 150 No
93PM 50(200) 50 1x50 200 No
93PM 50+50(100) 50 2x50 100 No
93PM 80(100) 80 2x40 100 No
93PM 80(150) 80 2x40 150 No
93PM 80(200) 80 2x40 200 No
93PM 80+40(150) 80 3x40 150 No
93PM 100(100) 100 2x50 100 No
93PM 100(150) 100 2x50 150 No
93PM 100(200) 100 2x50 200 No
93PM 100+50(150) 100 2x50 150 No
93PM 120(150) 120 3x40 150 No
93PM 120(200) 120 3x40 200 No
93PM 120+40(200) 120 4x40 200 No
93PM 150(150) 150 3x50 150 No
93PM 150(200) 150 3x50 200 No
93PM 150+50(150) 150 4x50 200 No
93PM 160(200) 160 4x40 200 No
93PM 200(200) 200 4x50 200 No
A single UPS frame can house maximum four UPMs, resulting in maximum
power rating of 200 kW. In addition, the UPS frames can be connected in
parallel to create even larger systems. A maximum of eight UPSs can be
connected in parallel.
UPS options and accessories
Eaton 93PM UPS 30–200 kVA
User's and installation guide
©
Eaton Corporation plc 2017. All rights reserved. Revision: 005 Document ID: P-164000249 33 (126)