Figure 44. Parts of the display
The display consists of the following parts:
1 Status bar The status bar displays the UPS name, state, current
date and time, meters information, and a sign in/out
button. It also shows any active alarms and warn-
ings.
2 Main navigation Select a screen by tapping on its name.
3 Content area This is the main area for showing information on the
UPS status and operations.
4 Status indicators See Section
7.1.2
.
7.1.2 Status indicators
The four symbols below the display are status indicators. They are colored light
emitting diode (LED) lamps, and they work in conjunction with the alarm horn to
let you know the operating status of the UPS.
Table 18: Status indicators
Indicator Status Description
Green symbol for normal
operation
On The UPS is operating normally and supplying pow-
er to the critical load.
Off The UPS is turned off.
Yellow symbol for battery
mode
On The UPS is in the battery mode. Because the bat-
tery mode is a normal condition of the UPS, the
green indicator for normal operation also remains
illuminated.
Eaton 93PM UPS 30–200 kVA User's and installation guide
©