Rated power
[kW]
Battery
Rated current [A] Maximum current* [A]
60 kVA 132 158
80 195 233
100 244 292
120 292 350
150 365 438
160 390 467
200 487 584
*Maximum battery current calculated at rated load and 1.67 V cell voltage for 36 block
string length.
Table 12: UPS power cable terminations
Terminal function Terminal Function
AC input to UPS rectifier X1 L1, L2, L3, N
AC input to bypass X2 L1, L2, L3, N
UPS output X3 L1, L2, L3, N
DC input from external bat-
tery to UPS
X4 battery +, battery -
Protective Earth PE PE
Note: External overcurrent protection is not provided by this product, but is
required by codes. Refer to Tables
8
and
9
for wiring requirements. If an
output lockable disconnect is required, it is to be supplied by the user.
Table 13: UPS power cable terminal bolt torques
UPS frame Function Tightening tor-
que [Nm]
Bolt size
93PM 30–50 kW, 60
kVA
X1: L1, L2, L3, X4
X1: N, X2, X3
14
12
PE 3
93PM 80–150 kW L1, L2, L3, N 47 M10
PE 24 M8
93PM 160–200 kW L1, L2, L3, N 80 M12
PE 47 M10
Eaton 93PM UPS 30–200 kVA User's and installation guide
©
Eaton Corporation plc 2017. All rights reserved. Revision: 005 Document ID: P-164000249 45 (126)