Rated
power [kW]
Rated
voltage [V]
Rectifier input UPS output / bypass
Rated
current [A]
Maximum
current [A]
Rated
current [A]
Maximum
current [A]
50 380 80 95 77 91
400 76 90 74 87
415 73 86 71 83
60 kVA 380 80 90 77 91
400 76 86 74 87
415 73 150 71 83
80 380 127 164 122 145
400 121 156 116 138
415 116 150 112 133
100 380 159 196 152 181
400 151 186 145 172
415 145 179 140 166
120 380 190 235 182 218
400 181 223 174 206
415 174 214 168 199
150 380 238 294 228 272
400 226 279 218 258
415 217 268 210 249
160 380 254 328 244 289
400 241 311 231 275
415 232 300 223 265
200 380 317 391 304 362
400 301 371 289 344
415 290 358 279 331
Notes:
1. Maximum rectifier current calculated at the -15% voltage tolerance and 102% continu-
ous overload.
2. Maximum output/bypass current calculated at continuous 125% overload and at -15%
voltage tolerance.
Table 11: Rated and maximum currents for rated power and voltage, battery
Rated power
[kW]
Battery
Rated current [A] Maximum current* [A]
30 73 88
40 97 117
50 122 146
Eaton 93PM UPS 30–200 kVA User's and installation guide
©
Eaton Corporation plc 2017. All rights reserved. Revision: 005 Document ID: P-164000249 44 (126)