EasyManua.ls Logo

Eaton 93PM - Page 21

Eaton 93PM
126 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
If the UPS becomes overloaded or unavailable, the UPS seamlessly switches to
the bypass mode and continues supplying the load through the static bypass.
The UPS automatically returns to the double conversion mode when the
abnormal condition, such as an extended time overload, is cleared and the
system operation is restored within the specified limits.
If a UPM within the UPS suffers an internal failure, the remaining UPMs
continue to support the load in the double conversion mode. The UPS is
automatically internally redundant when the UPS is not operating at full load.
However, if internal redundancy between the UPMs is not possible due to high
load, the UPS switches automatically to the bypass mode and remains in that
mode until the failure is corrected and the UPS is back in operation.
In an external parallel redundant system, each UPS can be isolated from the
system for service while the remaining UPSs support the load in the double
conversion mode.
3.2.1.2 Variable Module Management System mode
When Variable Module Management System (VMMS) mode is enabled, the load
is powered by UPMs in double conversion mode (see Figure
2
). The UPS
status indicated on the display is Unit Online VMMS and the UPM status is
Active.
UPS efficiency varies according to the load level at which the UPS operates.
VMMS technology enables achieving optimised system efficiency by
automatically optimising the UPM load level. As an example, when the load is
very low, a minimum of one UPM is online. This enhances the UPS system
efficiency by several percentage points.
The remaining UPMs are ready to switch to double conversion mode
instantaneously, if the load increases. The load will remain protected by double
conversion UPS the entire time, even during and after a load step.
It is possible to configure VMMS mode to include power module redundancy at
all times, so that a number of additional redundant UPMs are always online.
When the UPMs are in ready state, the IGBT converters are constantly
powered, since the rectifier input and inverter output contactors are closed. The
DC link is also powered. Only the IGBT gate signals are suspended. The only
step needed to come out of ready state is to gate the IGBT switches. Since DC
voltage is constantly present, the inverter is able to start instantaneously: the 2
ms transfer to double conversion is practically seamless.
3.2.1.3 Energy Saver System mode
Figure
3
shows the path of electrical power through the UPS system when the
UPS is operating in the Energy Saver System (ESS) mode.
Eaton 93PM UPS 30–200 kVA
User's and installation guide
©
Eaton Corporation plc 2017. All rights reserved. Revision: 005 Document ID: P-164000249 21 (126)

Table of Contents

Other manuals for Eaton 93PM

Related product manuals