avoid damages to the equipment or injuries to personnel, let only the
commissioning personnel do the connection of these batteries.
Note: See Section
9.5
for the battery specification.
WARNING
Do not connect battery strings with different battery quantity and voltage in
parallel.
For Eaton 93PM product line, there are three different battery cabinets available:
EBC-C, EBC-D and EBC-E. See a separate manual on instructions on how to
install Eaton external battery cabinets.
If you are installing a customer-supplied battery system, install the battery
system according to the battery and battery system manufacturer’s instructions
and all the applicable national codes and regulations. Only qualified personnel
can install the battery system. Battery cables must be protected against current
and thermal overload, that is, the battery system must include proper fuses or
breaker with protection function. Ground the external battery cabinet to the UPS.
The default battery settings of the UPS are for 12 V VRLA batteries. If you need
to use any other type of batteries, contact your Eaton representative.
30-100 kW models enable wiring the battery power cabling via the side panels, if
the UPS and the battery cabinet are installed side-by-side. See Figure
20
.
Figure 20. 30-100 kW and 60 kVA Side panel with battery power or battery signal wiring
wireway
Note: Obey the installation instructions in Section
4.3.2
.
Eaton 93PM UPS 30–200 kVA User's and installation guide
©
Eaton Corporation plc 2017. All rights reserved. Revision: 005 Document ID: P-164000249 63 (126)