LCD Interface Operation
Eaton ePDU G3 Operation Manual P-164000277—Rev 1 www.eaton.com/ePDU 54
Save the eNMC Hardware Configuration File to the USB
To save the eNMC module HW configuration file:
1. Make sure eNMC module is powered ON.
2. Insert a USB flash disk.
3. When the pop-up confirms that the file
is saved, click OK and press Enter to return to the Main Menu.(If
not confirmed within 10 sec, the USB flash disk is ignored by eNMC module.)
4. From the Settings menu, select USB Flash Mode.The module restarts.
5. Select Save eNMC file. When the file is saved, click OK to confirm.
6. Remove USB flash disk and select Ex
it.
7. After the file is saved from the eNMC module in the eNMC/config/hw path, verify the USB flash disk
cont
ains the file in the eNMC/config/hw directory located at root of USB flash disk (see Figure 58).
Figure 58. Verify HW File at USB Flash Drive Root
Load the eNMC Hardware Configuration File from the USB
To l oa d t he eNMC module hardware configuration file to the eNMC module from the USB Flash Drive:
1. Verify the USB flash disk contains eNMC/config/hw directory located at root of USB flash disk (see
Figure 58).
2. Make sure eNMC module is powered ON.
3. Insert a USB flash disk.
4. When the pop-up confirms that the USB is dete
cted, click OK then press Enter to return to the Main
Menu. (If not confirmed within 10 sec, the USB flash disk is ignored by eNMC module.)
5. From the Settings menu, select USB Flash Mode.The mod
ule restarts. (If there is no action within one
minute, the eNMC module exits the USB Flash mode. Unplug and repl
ug the USB flash disk to access this
menu again.)
6. Select Load eNMC file, then click OK to
start loading the eNMC file.
7. When the file is success
fully loaded, click OK in response to the confirmation message.
8. Remove the USB flash drive and select Exit.
NOTE 1 The eNMC/upgrade/hw directory contains only one file named epdu_cfg*.xml.
NOTE 2 epdu_cfg*.xml file shall be compatible with ePDU PN.