04/10 MN04020001Z-EN
Parameter menu (PAR)
117
P12.3 515 - DC braking, start frequency during delay ramp 1.50
0.00 - 10.00 Hz
The output frequency (f
Out
) set here automatically activates the DC
braking after a stop command (FWD/REV switched off).
Requirement: P6.8 = 1 (Stop function ramp).
The output frequency a is reduced after the stop command
according to the deceleration time set at P6.6. Depending on
inertia and the load torque, the speed of the motor b is reduced
accordingly and braked with DC current at the frequency value set
here.
You can set the duration of the DC braking c under P12.4.
PNU ID Access right
RUN
Value Description Factory setting
(P1.3)
f
t
f
out
f
t
P6.6
P6.8 = 1
P12.4
P12.3
FWD
REV
a
b
c