04/10 MN04020001Z-EN
Radio interference suppression 
filters
163
Special technical data for MMX-LZ...
Table 14: Special technical data for MMX-LZ...
Table 15: General rated operational data for MMX-LZ...
Part no.
Maximum mains 
supply voltage
Rated 
operational 
current
Maximum 
leakage 
current
Maximum 
contact 
current when 
the PE is 
broken
Max. power 
loss 
Weight  Size
U
LN
I
N
I
lk
1)
I
touch
2)
P
V
m
[V] [A] [mA] [mA] [W] [kg]
N F
MMX-LZ1-009 1 ~ 240 V + 10 %
(50/60 Hz)
9 a 17.6
b 1.7
14
2.2
31.2
4.3
3 0.8 FS1
MMX-LZ1-015 15 a 25.6
b 1.7
43.5
2.9
89
6.4
6 1.2 FS2
MMX-LZ1-017
17 a 25.6
b 1.7
43.5
2.9
89
6.4
10 2 FS3
MMX-LZ3-006 3 ~ 480 V + 10 %
(50/60 Hz)
6 7.3 6.3 170 3 0.8 FS1
MMX-LZ3-009 9 10.9 5.5 195 6 1.2 FS2
MMX-LZ3-022 22 10.9 5.5 195 10 2 FS3
1) RMS value of the leakage current to EN 60939
Only with MMX-LZ1: a = rated operation, b = leakage current (< 3.5 mA).
2) Peak value of the working current to EN 60939
N = peak value of the touch current present in normal operation with a PE conductor break
F = peak value of the worst case touch current with a PE conductor break or with a break of two or three phases with MMX-LZ3... o 
with a break of the N conductor on MMX-LZ1... .
Technical data Symbol
s used 
in 
technic
al data 
and 
formul
ae
Unit
Value
General
Mains frequency (f
LN
)f
LN
Hz 50/60
Environmental Conditions
Climate category IEC 25-100-21
Ambient temperature  i °C +40
Protection type
IP00
Connections
Power supply unit screw terminal
(L1, L2, L3, N)
mm
2
AWG
0.2 - 4
24 - 11
Tightening torque M Nm
fl-lbs
0.6 - 0.8
0.44 - 0.59
PE (mains side) M4 (screw)
Output lead to frequency inverter l mm
100
PE with ring cable lug (M4) l mm
65