EasyManuals Logo

Eaton MMX11 Series User Manual

Eaton MMX11 Series
199 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #90 background imageLoading...
Page #90 background image
Parameters
04/10 MN04020001Z-EN
86
P5.4 315 / Frequency monitoring 1 0
Monitoring of the selected frequency range.
A monitoring message can be implemented via the digital outputs
(value 10 = P5.1, P5.2, P5.3).
0 Deactivated
1 0.00 - P5.5 Hz
2 P5.5 - P6.4 Hz
P5.5 316 / Frequency monitoring 1, range 0.00
0.00 - P6.4 Hz
P5.6 346 / Frequency monitoring 2 0
Monitoring of the selected frequency range.
A monitoring message can be implemented via the digital outputs
(value 11 = P5.1, P5.2, P5.3).
0 Deactivated
1 0.00 - P5.7 Hz
2 P5.7 - P6.4 Hz
P5.7 347 / Frequency monitoring 2, range 0.00
0.00 - P6.4 Hz
Figure 78: Frequency monitoring (P5.5 - P5.7)
PNU ID Access right
RUN
Value Description Factory setting
(P1.3)
P5.5
P5.7
P5.4 = 1-
[Hz]
f
P5.4 = 2
P5.6 = 1-
P5.6 = 2
t

Table of Contents

Other manuals for Eaton MMX11 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton MMX11 Series and is the answer not in the manual?

Eaton MMX11 Series Specifications

General IconGeneral
BrandEaton
ModelMMX11 Series
CategoryDC Drives
LanguageEnglish

Related product manuals