Parameters
04/10 MN04020001Z-EN
86
P5.4 315 / Frequency monitoring 1 0
Monitoring of the selected frequency range.
A monitoring message can be implemented via the digital outputs
(value 10 = P5.1, P5.2, P5.3).
0 Deactivated
1 0.00 - P5.5 Hz
2 P5.5 - P6.4 Hz
P5.5 316 / Frequency monitoring 1, range 0.00
0.00 - P6.4 Hz
P5.6 346 / Frequency monitoring 2 0
Monitoring of the selected frequency range.
A monitoring message can be implemented via the digital outputs
(value 11 = P5.1, P5.2, P5.3).
0 Deactivated
1 0.00 - P5.7 Hz
2 P5.7 - P6.4 Hz
P5.7 347 / Frequency monitoring 2, range 0.00
0.00 - P6.4 Hz
Figure 78: Frequency monitoring (P5.5 - P5.7)
PNU ID Access right
RUN
Value Description Factory setting
(P1.3)
P5.5
P5.7
P5.4 = 1-
[Hz]
f
P5.4 = 2
P5.6 = 1-
P5.6 = 2
t