04/10 MN04020001Z-EN
Parameter menu (PAR)
93
P6.24 509 - Frequency jump 1, lower value (a). 0.00
0.00 - P6.4 Hz
P6.25 510 - Frequency jump 1, upper value (b). 0.00
P6.26 511 - Frequency jump 2, lower value (a). 0.00
0.00 - P6.4 Hz
P6.27 512 - Frequency jump 2, upper value (b). 0.00
0.00 - P6.4 Hz
P6.28 513 - Frequency jump 3, lower value (a). 0.00
0.00 - P6.4 Hz
P6.29 514 - Frequency jump 3, upper value (b). 0.00
0.00 - P6.4 Hz
91
a : P6.24, P6.26, P6.28
b : P6.25, P6.27, P6.29
In systems with mechanical resonances, you can cut out these
frequency ranges for stationary operation. Up to three different
frequency ranges can be set.
Figure 83: Setting range for frequency masking
PNU
ID Access right
RUN
Value Description Factory setting
(P1.3)
P6.30 759 - REAF, number of automatic restarts. 3
1 - 10
You can define here the permissible number of automatic restarts
(REAF = Restart After Failure).
P6.31 1481 - Manual mode, control level 1
Assignment of the control levels as per P6.1.
Manual mode is activated via parameter P3.37.
P6.32 1482 Manual mode, setpoint source 3
Assignment of setpoint sources as per P6.2.
Manual mode is activated via parameter P3.37.
P6.33 1483 Manual mode, KEYPAD blocked. 1
The Start/Stop functions are blocked in Manual mode via the
keypad.
0 Deactivated
1 Activated
PNU ID Access right
RUN
Value Description Factory setting
(P1.3)