26 Eaton PDI WaveStar BCMS Hub Installation and Operation Manual P-164001108—Rev 01
Figure 18. TIME Screen
To have the BCMS Hub use Simple Network Time Protocol (SNTP), follow these steps:
1. Press Time button at the bottom of the screen. The TIME screen displays (Figure 18).
2. Press the Server button. Enter the time server’s IP address.
3. Press the Zone button. Enter the time zone offset from Coordinated Universal Time (UCT) (-4 is Eastern
Daylight time).
4. Make sure the Use SNTP Server checkbox has a green check. Touch Use SNTP Server to toggle
between the green check (use SNTP Server) and red X (do not use SNTP Server).
5. Press Get to initialize time and verify that Time Synchronization is working.
6. Touch Set to confirm date/time.
7. Touch Save to save settings.
44..44 AAllaarrmm NNoottiiffiiccaattiioonn
When an alarm or warning is raised on any device monitored by the BCMS Hub, it is logged in the Event Log
and an alarm or warning symbol appears on the device line on the Home screen. Notification of new alarms or
warnings can also be sent by email or modem dial-out as a summary alarm, indicating simply that a new alarm
or warning has occurred somewhere in the Hub’s device chain. The user should check the Event Log and
Home screen for affected devices.