Eaton PDI WaveStar BCMS Hub Installation and Operation Manual P-164001108—Rev 01 35
55..66 PPaanneellbbooaarrdd DDeevviiccee IInnffoorrmmaattiioonn
RPPs and JCOMMs have points lists representing panelboards. The following points lists can be used with
BCMS Hub:
• Normal or Standard allows customization of warning and alarm levels for each panelboard circuit.
• KWH provides for accumulation of KWH data for each circuit, but warning and alarm levels are the same
for all panelboard circuits.
• IEC is specialized for IEC panelboards.
Operation: Device Information