EasyManua.ls Logo

Eaton Pow-R-Line SPX0370245 - Pulse Output (Solid State Relay Contacts); Digital Input Card (-2)

Eaton Pow-R-Line SPX0370245
584 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
www.eaton.com IM02601001E 7-5
Using the I/O Option Cards

The Pulse Output/Digital Input card is a combination of pulse outputs via solid state contacts and dry/wet contact
sensing digital inputs. The outputs are electrically isolated from the inputs and from the main unit.


Power consumption: 0.420W internal
Relay outputs
Number of outputs: 4
Contact type: Closing (SPST - NO)
Relay type: Solid state
Peak switching voltage: DC ±350V
Continuous load current: 120mA
Peak load current: 350mA for 10ms
On resistance, max.: 35Ω
Leakage current: 1µA@350V
Switching Rate max.: 10/s
Isolation: AC 3750V system to contacts
Reset/Power down state: Open contacts
Inputs
Number of inputs: 4
Sensing type: Wet or dry contact status detection
Wetting voltage: DC (12-24V), internally generated
Input current: 2.5mA – constant current regulated
Minimum input voltage: 0V (input shorted to common)
Maximum input voltage: DC 150V (diode protected against polarity reversal)
Filtering: De-bouncing with 50ms delay time
Detection scan rate: 100ms
Isolation: AC 2500V system to inputs

Operating Temperature: (-20 to +70) °C
Storage Temperature: (-40 to +80) °C
Relative air humidity: Maximum 95%, non-condensing
EMC - Immunity Interference: EN61000-4-2
Weight: 1.3oz
Dimensions (inch) W x H x L: 0.72 x 2.68 x 3.26
External Connection: AWG 12-26/(0.129 - 3.31)mm
2
13 pin, 3.5mm pluggable terminal block

The meter automatically recognizes the installed option card during Power Up. If you have not programmed a con-
guration for the card, the unit will default to the following outputs:
Status Inputs Defaulted to Status Detect
Pulse Outputs Defaulted to Energy Pulses
Pulse Channel 1 1.8 +Watt-hrs per pulse
Pulse Channel 2 1.8 -Watt-hrs per pulse
Pulse Channel 3 1.8 +VAR-hrs per pulse
Pulse Channel 4 1.8 -VAR-hrs per pulse

Table of Contents

Related product manuals