4-2 IM02601001E www.eaton.com
The PXM 2000 Series is designed to have Current Inputs wired in one of three ways. Diagram 4.1 shows the most
typical connection where CT Leads are terminated to the meter at the Current Gills. This connection uses Nickel-
Plated Brass Studs (Current Gills) with screws at each end. This connection allows the CT wires to be terminated
using either an “O” or a “U” lug. Tighten the screws with a #2 Phillips screwdriver. The maximum installation torque
is 1 Newton-Meter.
Other current connections are shown in Figures 4.2 and 4.3. Voltage and RS485/KYZ Connection is shown in
Figure 4.4.
Wiring Diagrams are shown later in this chapter.
Communications Connections are detailed in Chapter 5.
Current Gills
(Nickel-Plated Brass Stud)
Figure 4.1: CT Leads terminated to Meter, #8 Screw for Lug Connection
Electrical Installation