www.eaton.com IM02601001E 4-5

Voltage Inputs are connected to the back of the unit via a optional wire connectors. The connectors accomodate
AWG# 12 -26/ (0.129 - 3.31)mm
2
.
Figure 4.4: Voltage Connection

The meter’s Ground Terminals should be connected directly to the installation’s protective earth ground. Use AWG#
12/2.5 mm
2
wire for this connection.

Eaton recommends the use of fuses on each of the sense voltages and on the control power, even though the wiring
diagrams in this chapter do not show them.
Use a 0.1 Amp fuse on each voltage input.
Use a 3 Amp Slow Blow fuse on the power supply.
Power
Supply
Inputs
Voltage
Inputs
RS485 and
KYZ
Pulse Output

-

Electrical Installation