Using the PXM 2000 Series
The PT Setting has three parts: Pt-n (numerator), Pt-d (denominator), and Pt-S (scaling).
1. Press the Enter button when Pt is in the A window.
The PT-n screen appears. You can either:
• Change the value for the PT numerator.
• Access one of the other PT screens by pressing the Enter button: press Enter once to access the Pt-d
screen, twice to access the Pt-S screen.
a. To change the value for the PT numerator or denominator
From the Pt-n or Pt-d screen:
Use the Down button to select the number value for a digit.
• Use the Right button to move to the next digit.
b. To change the value for the PT scaling
From the Pt-S screen:
Use the Right button or the Down button to choose the scaling you want. The Pt-S setting can be 1, 10,
.
2. When the new setting is entered, press the Menu button twice.
3. The screen appears. Press Enter to save the new PT setting.
Example Settings:
277/277 Volts: Pt-n value is 277, Pt-d value is 277, Pt-S value is 1.
14,400/120 Volts: Pt-n value is 1440, Pt-d value is 120, Pt-S value is 10.
138,000/69 Volts: Pt-n value is 1380, Pt-d value is 69, Pt-S value is 100.
345,000/115 Volts: Pt-n value is 3450, Pt-d value is 115, Pt-S value is 100.
345,000/69 Volts: Pt-n value is 345, Pt-d value is 69, Pt-S value is 1000.
Pt-n and Pt-S are dictated by primary voltage; Pt-d is secondary voltage.
Use buttons to set Pt-n value Use buttons to set Pt-d value Use buttons to select scaling