Effective April 2010
10 Eaton Corporation www.eaton.com
Eaton SPD Series
Surge Protective Device for Integrated Units
Instruction Manual IM01005019E - Rev. 3
Description Specification
Surge current capacity per phase 50, 80, 100, 120, 160, 200, 250, 300, 400 kA ratings available
Nominal discharge current (I
n
) 20kA
Short circuit current rating (SCCR) 200kA
SPD Type Basic feature package = Type 1 (can also be used in Type 2 applications)
Standard and Standard with Surge Counter feature packages = Type 2
Standard split phase voltages available 120/240
Single phase 230
Three phase wye system voltages available 120/208, 127/220, 230/400, 277/480, 347/600
Three phase delta system voltages 240, 480, 600
Three phase high leg delta system voltages 120/240
Input Power Frequency 50/60 Hz
Power consumption (Basic units)
208Y, 220Y, 230L, 240S, 240D, and 240H voltage codes 0.5W
400Y and 480Y and 480D voltage codes 1.1W
600Y and 600D voltage codes 1.3W
Power consumption (Standard and Standard with Surge Counter units)
208Y, 220Y, 230L, 240S, 240D, and 240H voltage codes 0.6W
400Y, 480Y, and 480D Basic voltage codes 1.7W
600Y and 600D voltage codes 2.1W
Protection modes Single split phase .....................L-N, L-G, N-G, L-L
Single phase .............................L-N, L-G, N-G
Three phase Wye...................... L-N, L-G, N-G, L-L
Three phase delta......................L-G, L-L
Three phase high leg delta........L-N, L-G, N-G, L-L
Maximum continuous operating voltage (MCOV)
208Y, 220Y, 240S, 240D, and 240H voltage codes 150 L-N,150 L-G, 150 N-G, 300 L-L
230L, 400Y and 480Y voltage codes 320 L-N, 320 L-G, 320 N-G, 640 L-L
600Y voltage code 420 L-N, 420 L-G, 420 N-G, 840 L-L
240 D voltage code 320 L-G, 320 L-L
480 D voltage code 640L- L-G, 640 L-L
600D voltage code 840 L-G, 840 L-L
Ports 1
Operating temperature -40 through 50° C (-40 through 122° F)
Operating humidity 5% through 95%, non-condensing
Operating altitude Up to 16,000 ft (5000 m)
Seismic withstand capability Meets or exceeds the requirements specified in the IBC
®
2006, CBC 2007, and UBC
®
Zone 4
Weight 50-200kA - Approximately 1.6 kg (3.5 lbs) 250 - 400kA - Approximately 3.2kg (7.0 lbs)
Form C relay contact ratings
150 Vac or 125 Vdc, 1A maximum
Form C relay contact loogic Power on, normal state - NO contact = OPEN, NC contact = CLOSED
Power off, fault state, - NO contact = CLOSED, NC contact = OPEN
EMI/RFI filtering attenuation (Standard and Standard With Surge Counter Up to 50 dB from 10 kHz to 100 MHz
Agency certifications and approvals UL1449 3rd Edition recognized component for the US and Canada, UL1283 (Type 2 SPDs only)
Warranty 10 Years
5.0 Specifications
Table 4. Specifications

Table of Contents

Related product manuals