6-10 IM02601001E www.eaton.com
Using the PXM 2000 Series
Using Operating Mode
Operating Mode is the PXM 2000 Series’ default mode, that is, the standard front panel display. After Startup, the
meter automatically scrolls through the parameter screens, if scrolling is enabled. Each parameter is shown for
7 seconds, with a 1 second pause between parameters. Scrolling is suspended for 3 minutes after any button is
pressed.
1. Press the Down button to scroll all the parameters in Operating Mode. The currently “Active,” i.e., displayed,
parameter has the Indicator light next to it, on the right face of the meter.
2. Press the Right button to view additional readings for that parameter. The table below shows possible
readings for Operating Mode. Sheet 2 in
Appendix A
shows the Operating Mode Navigation Map.
Readings or groups of readings are skipped if not applicable to the meter type or hookup, or if
they are disabled in the programmable settings.

POSSIBLE READINGS
VOLTS L-N VOLTS_LN VOLTS_
LN_MAX
VOLTS_
LN_MIN
VOLTS_
LN_THD
VOLTS L-L VOLTS_LL VOLTS_LL_
MAX
VOLTS_LL_
MIN
AMPS AMPS AMPS_
NEUTRAL
AMPS_
MAX
AMPS_MIN AMPS_THD
W/VAR/PF W_VAR_PF W_VAR_
PF_MAX_
POS
W_VAR_
PF_MIN_
POS
W_VAR_
PF_MIN_
NEG
VA/Hz VA_FREQ VA_FREQ_
MAX
VA_FREQ_
MIN
Wh KWH_REC KWH_DEL KWH_NET KWH_TOT
VARh KVARH_
POS
KVARH_
NEG
KVARH_
NET
KVARH_
TOT
VAh KVAH