9-12 IM02601001E www.eaton.com
Functions on the Web Server Pages
Events
The Power Xpert Meter monitors and logs  and  events
Events can be used to send e-mail as well as to change the state of internal or external I/
Os.
Triggers
The following sections highlight available triggers. The meter will use the programmed
limits set by the user. Every event and its corresponding parameters along with the date
and time of the occurrence are logged and available for display or retrieval.
Triggers are congured in the Setup page. Each trigger can have the following limits:
Upper Critical Limit
Upper Cautionary Limit
Lower Cautionary Limit
Lower Critical Limit
In addition, you can select:
If alarms are enabled for this data.
If the limits simply trigger an event (not an alarm).
If the alarm/event closes automatically when the value falls below the high limits or
above the low limits. If not, a user must acknowledge the alarm to remove it from the
active list.
In addition, alarms and events will generate an RSS feed and can generate email and
alerts. See the Setup on the Web Pages chapter for setup details for triggers, I/O, and
E-mail.

The Power Xpert
®
Meter monitors and logs events for the following triggers:
Ia Demand Ia Peak Ib
Demand Ib Peak Ic Demand Ic Peak
In Iavg Vab
Van Vbc Vbn
Vca Vcn V(L-L) Average
V(L-N) Average Avg. Negative PF Avg Positive PF
Demand Current (3 Phase
Avg)
Demand Forward Watts Demand Ia
Demand Ib Demand Ic Demand In
Demand In Peak Demand Lagging VARs Demand Leading VARs
Demand Net VARs Demand Net Watts Demand Reverse Watts
Demand Sum VARs Demand Sum Watts Demand VAs
Frequency Percent THD Ib Percent THD Ic
PF App Phase A PF App Phase B PF App Phase C
PF Apparent Peak Demand Amps Avg Peak Demand Forward
Watts
Peak Demand Lagging
VARs
Peak Demand Leading
VARs
Peak Demand Net VARs

Table of Contents