Functions on the Web Server Pages

From the Power page, click one of the radio buttons on the left side of the page that rep-
resents the type of power measurement you want to view. The page will update to display
a graph with minimum, maximum and average values as per the selection.
Power Factor (Apparent)

The  page contains information about the present power quality for PXM2260 and
2270 meters. These meters calculate the following instantaneous values, averaged over
a period of 60 cycles:
Percent THD of Current for Phases A, B, and C
Percent THD of Voltage for Phases A, B, and C.
Using the drop-down box above the graph, you can select to view this information as a
trend, with minimum and maximum values, or as harmonics.
The PXM2250 meter does not measure %THD.
THD
The Total Harmonic Distortion (THD) is the ratio, expressed as a percentage, of the rms
value of the ac signal after the fundamental component is removed and inter-harmonic
components are ignored to the rms value of the fundamental. The formula for THD is
provided below. The variables X
1
and x
n
may represent either voltage or current and may
be expressed either as rms or peak values, as long as all are expressed in the same
fashion.