10-6 IM02601001E www.eaton.com
Setup on the Web Server Pages
In addition to setpoints and alarm messages, you can also set the hysteresis. This is set
as a percentage, and is used to dampen “noise” events caused by a value bouncing back
and forth across a set point.
Out of Limits Setup Edit Page

Use the  page to congure device, option card, or communica-
tions status event triggers. You can congure if such events are to be treated as alarms,
what the alarm levels are, the messages associated with the events, the limit values, and
if the alarms are to be autoclosing. These alarms include:
Restart is pending
Modbus RTU communications failure
Alarms based on the state of digital inputs.