Introduction
1-2
EATON Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201554 Rev E powerware.com
1.1 Basic System Configurations
The following basic UPS system configurations are possible:
Single module UPS and one to four battery cabinets
Single module UPS with UPS Sidecar (maintenance bypass or 1+1 tie configuration) and
one to four battery cabinets
Single module UPS, one to four battery cabinets, and an optional Integrated Distribution
Cabinet (IDC)
Single module UPS, one to four battery cabinets, and an optional Integrated Accessory
Cabinet (IAC) (maintenance bypass, 1+1 tie, or 1+1 tie with maintenance bypass
configuration)
Single module UPS, one to four battery cabinets, and an optional Integrated Accessory
Cabinet (IAC) (distribution configuration)
Powerware Hot Sync parallel system with two UPS modules, one to four battery cabinets
for each UPS, and an optional module tie cabinet
- One capacity/one redundant (1+1)
- Two capacity (2+0)
Powerware Hot Sync parallel system with three UPS modules, one to four battery
cabinets for each UPS, and an optional module tie cabinet
- Two capacity/one redundant (2+1)
- Three capacity (3+0)
Powerware Hot Sync parallel system with four UPS modules, one to four battery cabinets
for each UPS, and an optional module tie cabinet
- Three capacity/one redundant (3+1)
- Four capacity (4+0)
Powerware Hot Sync parallel system with two UPS modules, one to four battery cabinets
for each UPS, an optional module tie cabinet, and an optional IDC
- One capacity/one redundant (1+1)
- Two capacity (2+0)
Powerware Hot Sync parallel system with three UPS modules, one to four battery
cabinets for each UPS, an optional module tie cabinet, and an optional IDC
- Two capacity/one redundant (2+1)
- Three capacity (3+0)
Powerware Hot Sync parallel system with four UPS modules, one to four battery cabinets
for each UPS, an optional module tie cabinet, and an optional IDC
- Three capacity/one redundant (3+1)
- Four capacity (4+0)
The UPS system configuration can be enhanced by adding optional accessories such as a
Remote Emergency Power-off (REPO) control, Remote Monitor Panel II (RMP II), or X-Slot
®
communication cards.

Table of Contents

Other manuals for Eaton Powerware 9390

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton Powerware 9390 and is the answer not in the manual?

Eaton Powerware 9390 Specifications

9390-40-N

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity40/36 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions519x1872x804 mm
weight UPS257 kg

9390-60-U

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity60/54 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions519x1872x804 mm
weight UPS313 kg

9390-80-N

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity80/72 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions519x1872x804 mm
weight UPS313 kg

9390-100-U

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity100/90 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions900x1872x804 mm
weight UPS480 kg

9390-120-N

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity120/108 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions900x1872x804 mm
weight UPS480/530 kg

9390-160-N

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity160/144 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions900x1872x804 mm
weight UPS530 kg