1-1
EATON Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201554 Rev E powerware.com
Chapter 1 Introduction
The Powerware
®
9390 uninterruptible power supply (UPS) is a true online, continuous -duty,
transformerless, double-conversion, solid-state, three-phase system, providing conditioned
and uninterruptible AC power to protect the customer’s load from all nine power failures.
The Powerware 9390 UPS is available as a single module or a multiple module parallel
system (see paragraph 1.1).
The Powerware online power protection system is used to prevent loss of valuable
electronic information, minimize equipment downtime, and minimize the adverse effect on
production equipment due to unexpected power problems.
The Powerware 9390 UPS continually monitors incoming electrical power and removes the
surges, spikes, sags, and other irregularities that are inherent in commercial u tility power.
Working with a building’s electrical system, the UPS system supplies clean, consistent
power that sensitive electronic equipment requires for reliable operation. During
brownouts, blackouts, and other power interruptions, batteries provide emergency power
to safeguard operation.
The UPS system is housed in a single, free-standing cabinet with safety shields behind the
door for hazardous voltage protection. The cabinet matches the battery and distribution
cabinets in style and color and can be installed in line-up-and-match or standalone
configurations. Figure 1 -1 shows the Powerware 9390 UPS (100–160 kVA).
Figure 1-1. Powerware 9390 UPS (100–160 kVA) Cabinet

Table of Contents

Other manuals for Eaton Powerware 9390

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton Powerware 9390 and is the answer not in the manual?

Eaton Powerware 9390 Specifications

9390-40-N

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity40/36 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions519x1872x804 mm
weight UPS257 kg

9390-60-U

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity60/54 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions519x1872x804 mm
weight UPS313 kg

9390-80-N

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity80/72 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions519x1872x804 mm
weight UPS313 kg

9390-100-U

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity100/90 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions900x1872x804 mm
weight UPS480 kg

9390-120-N

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity120/108 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions900x1872x804 mm
weight UPS480/530 kg

9390-160-N

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity160/144 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions900x1872x804 mm
weight UPS530 kg

Related product manuals