Product Specifications
15-3
EATON Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201554 Rev E powerware.com
15.3 Multiple Module Parallel Specifications
15.3.1 UPM Input
Same as single module.
15.3.2 UPM Output
Same as single module.
15.3.3 Environmental
Same as single module.
15.3.4 Battery
Same as single module.
15.3.5 Module Tie Cabinet Input
Operating Input Voltage
(UPM Dependent)
208 Vac for operation from 177 Vac to 229 Vac
220 Vac for operation from 187 Vac to 242 Vac
480 Vac for operation from 408 Vac to 528 Vac
Operating Input Current
See Appendix A, Table O through Table Q.
15.3.6 Module T ie Cabinet Output
Operating Output Voltage
(UPM Dependent)
208 Vac for operation from 177 Vac to 229 Vac
220 Vac for operation from 187 Vac to 242 Vac
480 Vac for operation from 408 Vac to 528 Vac
Operating Output Current
See Appendix A, Table O through Table Q.