8-1
EATON Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201554 Rev E powerware.com
Chapter 8 Features, Options, and Accessories
8.1 UPS Standard Features
The UPS has many standard features that provide cost-effective and consistently reliable
power protection.
8.1.1 Control Panel
The control panel, located on the UPS front door, contains an LCD and pushbutton
switches to control the operation of the UPS, and to display the status of the UPS system.
See Chapter 9, “Using the Control Panel,” for additional information.
8.1.2 Customer Interface
8.1.2.1 Building Alarm Monitoring
The facility’s alarm system contacts can be connected to two inputs in the UPS. The UPS
uses these inputs to monitor the building alarms in addition to the UPS status. See
Chapter 11, “Using Features and Options,” for additional information.
8.1.2.2 Alarm Contact
One alarm contact is provided for connection to equipment at the facility, such as a light,
an audible alarm, or a computer terminal. The equipment connected to this contact alerts
you to a UPS alarm. See Chapter 11, “Using Features and Options,” for additional
information.
8.1.3 X-Slot Communication Bay
A two-slot communication bay is standard equipment, with an additional two-slot bay
available as an option with the installation of a mini-CSB. Two to four optional X-Slot cards
can be installed in the UPS module at any time. See Chapter 13, “Communication,” for
additional information.
8.1.4 ConnectUPS-X Web/SNMP Card X-Slot Card
AConnectUPS-XWeb/SNMPCardisprovidedasstandardequipmentandprovidesremote
monitoring through a Web browser interface, e -mail, and a network management system
(NMS) using SNMP. See Chapter 13, “Communication,” for additional information.
t

Table of Contents

Other manuals for Eaton Powerware 9390

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton Powerware 9390 and is the answer not in the manual?

Eaton Powerware 9390 Specifications

9390-40-N

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity40/36 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions519x1872x804 mm
weight UPS257 kg

9390-60-U

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity60/54 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions519x1872x804 mm
weight UPS313 kg

9390-80-N

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity80/72 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions519x1872x804 mm
weight UPS313 kg

9390-100-U

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity100/90 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions900x1872x804 mm
weight UPS480 kg

9390-120-N

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity120/108 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions900x1872x804 mm
weight UPS480/530 kg

9390-160-N

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity160/144 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions900x1872x804 mm
weight UPS530 kg