Maintaining the UPS System
14-2
EATON Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201554 Rev E powerware.com
Determine if the battery is inadvertently grounded. If it is, remove the source of the
ground. Contact with any part of a grounded battery can result in electrical shock. The
likelihood of such shock is reduced if such grounds are removed during installation and
maintenance.
When replacing batteries, use the same number of sealed, lead-acid batteries.
Proper disposal of batteries is required. Refer to your local codes for disposal
requirements.
WARNING
HAZARDOUS WASTE. Do not incinerate or dispose of batteries indiscriminately. Observe
local and national codes.
Do not dispose of battery or batteries in a fire. The battery may explode.
Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin
and eyes, and may be toxic.
A battery can cause electrical shock, burn from high short-circuit current, or fire. Observe
proper precautions.
ATTENTION!
Une batterie peut prêsenter un risque de choc êlectrique, de brulure, ou d’incendie. Suivre
les précautions qui s’imposent.
Pour le remplacement, utiliser le même nombre et modéle des batteries.
L’élimination des batteries est règlementée. Consulter les codes locaux à cet effet.
14.2 Performing Preventive Maintenance
The UPS system requires very little preventive maintenance. However, the system should be
inspected periodically to verify that the units are operating normally and that the batteries
are in good condition.
14.2.1 DAILY Maintenance
Perform the following steps daily:
1. Check the area surrounding the UPS system. Ensure the area is not cluttered,
allowing free access to the unit.
2. Ensuretheairintakes(ventsonthefront doors) and exhaust opening (on top of
the UPS cabinet sections) are not blocked.

Table of Contents

Other manuals for Eaton Powerware 9390

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton Powerware 9390 and is the answer not in the manual?

Eaton Powerware 9390 Specifications

9390-40-N

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity40/36 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions519x1872x804 mm
weight UPS257 kg

9390-60-U

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity60/54 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions519x1872x804 mm
weight UPS313 kg

9390-80-N

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity80/72 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions519x1872x804 mm
weight UPS313 kg

9390-100-U

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity100/90 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions900x1872x804 mm
weight UPS480 kg

9390-120-N

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity120/108 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions900x1872x804 mm
weight UPS480/530 kg

9390-160-N

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity160/144 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions900x1872x804 mm
weight UPS530 kg