Features, Options, and Accessories
8-4
EATON Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual S 164201554 Rev E powerware.com
8.2.8 Remote Monitor Panel II
An optional RMP II contains backlit status indicators and a local horn, allowing you to
monitor the operational status and alarm condition of the UPS from virtually any location
within your facility. This option is described further in Chapter 11, “Using Features and
Options.”
8.2.9 Relay Interface Module II
An optional RIM II uses relay contact closures to indicate the operating status and alarm
condition of the UPS. This option is described further in Chapter 11, “Using Features and
Options.”
8.2.10 Supervisory Contact Module II
An optional SCM II establishes an interface between the UPS system equipment and the
customer’s monitor. This option is described further in Chapter 11, “Using Features and
Options.”
8.3 Symbols, Controls, and Indicators
The following are examples of symbols used on the UPS or accessories to alert you to
important information:
RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and
the associated warning should be observed.
CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your operator’s manual
for additional information, such as important operating and maintenance
instructions.
This symbol indicates that you should not discard the UPS or the UPS batteries
in the trash. This product contains sealed, lead-acid batteries and must be
disposed of properly. For more information, contact your local recycling/reuse
or hazardous waste center.
This symbol indicates that you should not discard waste electrical or electronic
equipment (WEEE) in the trash. For proper disposal, contact your local
recycling/reuse or hazardous waste center.

Table of Contents

Other manuals for Eaton Powerware 9390

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton Powerware 9390 and is the answer not in the manual?

Eaton Powerware 9390 Specifications

9390-40-N

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity40/36 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions519x1872x804 mm
weight UPS257 kg

9390-60-U

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity60/54 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions519x1872x804 mm
weight UPS313 kg

9390-80-N

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity80/72 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions519x1872x804 mm
weight UPS313 kg

9390-100-U

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity100/90 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions900x1872x804 mm
weight UPS480 kg

9390-120-N

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity120/108 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions900x1872x804 mm
weight UPS480/530 kg

9390-160-N

Battery IconBattery
battery capacity 55 Ah1270 kg
battery capacity 67 Ah1430 kg
battery capacity 125 Ah2350 kg
Power IconPower
capacity160/144 kVA/kW
nominal input voltage220/380, 230/400, 240/415 VAC
input voltage range-15%, +10% from nominal at 100% load
Operating Environment IconOperating Environment
operating temperature0°C to +40°C, +45°C with 7, 5% derating
storage temperature-15°C to +45°C
altitude< 1500 m
Weight and Dimensions IconWeight and Dimensions
dimensions900x1872x804 mm
weight UPS530 kg

Related product manuals