Installation
18 S811+ Soft Starter MN03900001E—November 2012
Using Auxiliary Contacts
Often these contacts are used as shown in the illustrations 
on this page with indicating lamps. In some installations the 
user may wish to use an electromagnetic relay for indication 
of the status at a remote location for use by a programmable 
controller (PLC), or in a 120 Vac control circuit. 
If the S811+ Soft Starter is subject to mechanical shock 
during operation, it is possible that these contacts may 
momentarily open, causing nuisance fault tripping of down 
stream devices. When used with an indicating lamp, a 
momentary contact opening would not be observed. In order 
to assure proper application, it is suggested that the 
following recommendations be implemented: 
PLC Interface—It is suggested that a 20 ms delay be 
programmed to assure the contact status before a change of 
status is indicated. The application and the environmental 
issues will determine the exact requirements. 
120 Vac Signal Control—When a relay is used in 
conjunction with an electronic control, it is highly 
recommended that a noise suppressor be used across the 
relay coil. In the case of an AC coil, the noise suppressor is 
made up of a series connected resistor and capacitor as 
shown in the figure below. Usually the delay in the relay 
opening is very small, so if the system is subject to shock, a 
delay should be added in the external control before the 
contact change of state is recognized. The resistor is rated 
100 ohms at 0.5 watts. The capacitor is 0.25 μF at 250 Vac. 
120 Vac Control
24 Vdc Signal Control—When a relay is used in conjunction 
with an electronic control, it is highly recommended that a 
noise suppression/snubber diode be placed across the relay 
coil as shown below. This diode offers two benefits. First, 
the suppression of any electrical noise generated when the 
relay coil is de-energized. Second, the diode delays the 
opening of the relay slightly as it dissipates the energy stored 
in the relay coil. This delay is often long enough to 
compensate for the potential effects of a mechanical shock 
opening the control contact. A typical suppression diode is a 
1N4001. 
24 Vdc Control