Appendix A—Parameters
S811+ Soft Starter MN03900001E—November 2012 53
Network Setup Menu
Network Setup
Network Setup Minimum Maximum Default Notes
Access
Level
Comm Loss Action 0 7 0 0 = Auto Stop
1 = Auto Run1
2 = Unavailable
3 = Hold Last
4 = Unavailable
5 = Unavailable
6 = Unavailable
7 = All Stop Fault
2
Modbus Baud Rate 0 7 4 0 = 1200
1 = 2400
2 = 2800
3 = 9600
4 = 19200
5 = 38400
6 = 57600
7 = 115200
2
Modbus Address 0
Modbus Parity 0 1 0 0 = Even (1 stop bit)
1 = Odd (1 stop bit)
2
Modbus Stop Bits 1 2 1 2
Modbus Mode 2
Config CRC 0
Firmware Version 0
Hardware Version 0
Discrete Input 0
Discrete Output 0
Motor Status 0
Modbus User Name 2
Product Code 0
Network 2 Enable 0 1 0 0 = disabled, register 500 active
1 = enabled, register 501 active
2