Appendix A—Parameters
S811+ Soft Starter MN03900001E—November 2012 53
Network Setup Menu
Network Setup 
Network Setup Minimum Maximum Default Notes
Access 
Level
Comm Loss Action 0 7 0 0  = Auto Stop
1  =  Auto Run1
2  =  Unavailable
3  =  Hold Last
4  =  Unavailable
5  =  Unavailable
6  =  Unavailable
7  =  All Stop Fault
2
Modbus Baud Rate 0 7 4 0  =  1200
1  =  2400
2  =  2800
3  =  9600
4  =  19200
5  =  38400
6  =  57600
7  =  115200
2
Modbus Address 0
Modbus Parity 0 1 0 0  =  Even (1 stop bit)
1  =  Odd (1 stop bit)
2
Modbus Stop Bits 1 2 1 2
Modbus Mode 2
Config CRC 0
Firmware Version 0
Hardware Version 0
Discrete Input 0
Discrete Output 0
Motor Status 0
Modbus User Name 2
Product Code 0
Network 2 Enable 0 1 0 0  =  disabled, register 500 active
1  =  enabled, register 501 active
2