Functional Description
S811+ Soft Starter MN03900001E—November 2012 27
Control Functions
Network Control
When the S811+ is in Network control and a 24 Vdc signal is 
present at control block terminal “P”, it is ready to respond 
to motor START control commands issued through the 
Network Comms Port. 
The Local Control must be disabled to allow Network control. 
Local Control is available for configuration through a 
programmable function on the control terminal block 
(default—terminal #3) or enabling the Local Ctrl Only 
parameter in the Advanced I/O Menu.
The Comms Port enables complete communications 
between the S811+ and the Network including changing 
parameters settings, issuing control commands, and 
monitoring selected operational values via ModBus, or other 
networks. The Comms Port provides ModBus motor control 
commands as the native protocol. 
Local Control
S811+ Local Control (default) consists of Permissive, Start, 
Jog, Local and Reset 24 Vdc control commands to the 
Terminal Block. The S811+ can also be started/stopped from 
the Digital Interface Module. 
The default configuration of the Control Terminal Block 
utilizes five (5) functions to control the S811+ soft starter. 
Terminals 1 thru 4 may be (re)programmed for other 
functions.
Terminal P–Permissive (run enable)—Must be energized 
with 24 Vdc to enable operation of the S811+ soft starters by 
either local and/or network control. If power is lost or 
removed from Permissive terminal at any time, the unit will 
initiate a coast Stop, Soft Stop, or Pump Stop in accordance 
with the setup parameter selections. If the S811+ is being 
controlled from a network, loss of the Permissive signal will 
initiate a coast Stop, Soft Stop, or Pump Stop in accordance 
with the setup parameter selections. Functionality of this 
terminal cannot be changed.
Terminal 1—Start (default)—If 24 Vdc is present at the 
Permissive terminal, momentary application of 24 Vdc to the 
Start terminal will initiate a Voltage Ramp or Current Limit 
start for the S811+ soft starter. Application of 24 Vdc may be 
maintained
Note: With level sensing control, if 24 Vdc is lost or removed 
from the Permissive terminal at any time, the unit will 
initiate a stop in accordance with setup parameter 
selections. A restart may occur when 24 Vdc is 
restored or reapplied if: 
a) 24 Vdc is present on the Start terminal 
(maintained), and;
b) the S811+ shows a Ready LED (not faulted) status. 
If the starter has faulted and the fault condition 
clears AND the Auto Reset Mode parameter in the 
Operation Mode list is set to AUTO, the starter will 
restart. 
See the Edge and Level Sensing sections on Page 28 
for additional details. 
If the AUTO Reset Mode setting is used with level 
sensing, CAUTION must be exercised to assure 
that any restart occurs in a safe manner. Motor 
restart may occur immediately and unexpectedly 
after any fault condition has cleared.
Terminal 2—Jog (default)—Application of 24 Vdc power to 
the Jog terminal will apply a Start command for as long as 
the signal is present. The S811+ will perform a Start ramp in 
accordance with Start parameters. If the motor achieves 
synchronous speed, the internal bypass contactors will not 
close. When the 24 Vdc signal is removed, the soft starter 
will perform a coast stop, irrespective of any Soft Stop or 
Pump Stop parameter values.
Terminal 3—Local (default)—Application of 24 Vdc power to 
the L
ocal terminal will allow Start or Jog control from the 
terminal block. 
Note: Local Control only may be enabled by the Local Ctrl 
Only parameter in the Advanced I/O menu. If this 
parameter is enabled, control commands from any 
network will not be recognized.
Terminal 4—Reset (default)—Application of 24 Vdc power to 
the Reset terminal will reset the soft starter after all fault 
conditions are cleared and no active fault is present. If the 
Fault LED is not able to be reset, a fault condition still exists 
and must be corrected. A Reset signal may also be sent from 
any network connection.