Appendix G—Modbus Register Map
68 S811+ Soft Starter MN03900001E—November 2012
Scaled Average Three Phase
Currents in amps—Pole
2 352 R UINT16 Scaled Average pole current in Amps
Scaled Three Phase Currents in
amps—Pole
2 353 R UINT16 L1 RMS pole current in Amps
2 354 R UINT16 L2 RMS pole current in Amps
2 355 R UINT16 L3 RMS pole current in Amps
Scaled Average Three Phase
Currents in deciamps—Pole
2 356 R UINT16 Scaled Average pole current in 0.1 Amps
Scaled Three Phase Currents in
deciamps—Pole
2 357 R UINT16 L1 RMS pole current in 0.1 Amps
2 358 R UINT16 L2 RMS pole current in 0.1 Amps
2 359 R UINT16 L3 RMS pole current in 0.1Amps
Power Factor 2 360 R SINT16 0 to 1.0000 (in 0.0001)
Integer Average Three Phase Real
Power kW
2 361 R UINT16 Average Real Power (kW)
Power Device Pole
Temperature
2 362 R SINT16 L1 pole temp in 0.1°C
2 363 R SINT16 L2 pole temp in 0.1°C
2 364 R SINT16 L3 pole temp in 0.1°C
DC Control Voltage 2 365 R UINT16 DC voltage reported in 0.001V
Device Temperature in Degrees C 2 366 R SINT16 Device temp in 0.1°C
Auto Reset Count 2 367 R UINT16 # of times S811+ has been auto reset
Line Frequency 2 368 R UINT16 Line Frequency (in 0.01Hz)
Line Phase Sequence 1 369 R UINT8 0x01—ABC Phase sequence
0x02—ACB Phase sequence
Fault List
(Fault/Warning codes will be
repeated in the list)
2 370 R UINT16 Latest Fault/Warning code
2 371 R UINT16 2nd Latest Fault/Warning code
2 372 R UINT16 3rd Latest Fault/Warning code
2 373 R UINT16 4th Latest Fault/Warning code
2 374 R UINT16 5th Latest Fault/Warning code
2 375 R UINT16 6th Latest Fault/Warning code
2 376 R UINT16 7th Latest Fault/Warning code
2 377 R UINT16 8th Latest Fault/Warning code
2 378 R UINT16 9th Latest Fault/Warning code
2 379 R UINT16 10th Latest Fault/Warning code
Application Status 2 380 R UINT16 Applications status (present fault)
Motor RUN1input level sense
enable
1 381 R UINT8 0x00—edge sense
0x01—level sense
Modbus Motor Control (3-Wire) 1 500 R/W UINT8 bit
0
1
2
3
4
5
6
7
Description
Run1
Run2
Permissive
Fault Reset
reserved
reserved
reserved
Ramp2 enable
Register Map, continued
Parameter
Data
Length
Modbus
Register
Number Read/Write
Data
Type Description