Appendix G—Modbus Register Map
70 S811+ Soft Starter MN03900001E—November 2012
Motor Start Method 1 608 R/W UINT8 0 = Voltage Ramp
1 = Current Limit
2 = Unavailable
3 = Pump Start (w pump option)
Percent Initial Torque 1 609 R/W UINT8 0–100%
Motor Start Ramp Time 2 610 R/W UINT16 0.5–180s (in 0.1 sec)
Motor Stop Ramp Time 2 611 R/W UINT16 0.0–60.0s (in 0.1 sec)
Motor Pump Stop Time 2 612 R/W UINT16 20.0–120.0 (in 0.1 sec)
Kick Start Initial Torque 1 613 R/W UINT8 0–100%
Kick Start Time 1 614 R/W UINT8 0.0–2.0 sec (in 0.1 sec)
Ramp2 Motor Phase Sequence 1 615 R/W UINT8 0 = ABC Phase sequence
1 = ACB Phase sequence
Ramp2 Motor Start Method 1 616 R/W UINT8 0 = Voltage Ramp
1 = Current Limit
2 = Unavailable
3 = Pump Start (w pump option)
Ramp2 Motor Percent Initial
Torque
1 617 R/W UINT8 0–100%
Ramp2 Motor Start Ramp Time 2 618 R/W UINT16 0.5–180s (in 0.1 sec)
Ramp2 Motor Stop Ramp Time 2 619 R/W UINT16 0.0–60.0s (in 0.1 sec)
Ramp2 Motor Pump Stop Time 2 620 R/W UINT16 20.0–120.0 (in 0.1 sec)
Ramp2 Motor Kick Start Initial
Torque
1 621 R/W UINT8 0–100%
Ramp2 Motor Kick Start Time 1 622 R/W UINT8 0.0–2.0 sec (in 0.1 sec)
Motor Control Terminal Block
Local Control Enable
1 623 R/W UINT8 1 = local control only enabled
0 = disable(terminal block input selects local/network
control)
Motor Control Input Configuration
S811 input#1 cfg
S811 input#2 cfg
S811 input#3 cfg
S811 input#4 cfg
Network input#1 cfg
Network input#2 cfg
Network input#3 cfg
Network input#4 cfg
2
2
2
2
2
2
2
2
624
625
626
627
628
629
630
631
RW
RW
RW
RW
RW
RW
RW
RW
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
UINT16
0 = No function
1 = Run1
2 = Ramp2
3 = Jog
4 = Local control enable
5 = Fault reset
6 = E-stop input
7 = Alarm-No-Trip
8 = External Trip
9 = External Warning
10 = Disable overload on start
11 = Analog Input (S811 input #4 only)
Analog Input Data Range 1 632 R/W UINT8 Value
0x01
0x02
0x03
Description
not supported
0–20 mA range
4–20 mA range
Register Map, continued
Parameter
Data
Length
Modbus
Register
Number Read/Write
Data
Type Description