INSTRUCTIONS MANUAL
-34-
NOTE: If DATABASE is installed, can be used to insert the value of refrigerant into the GAS
FILLING field.
Edit REFRIGERANT CHARGE MODE:
Select the connection mode:
- HP+LP fill the refrigerant from both HP and LP service ports
- HP to fill the refrigerant only from the HP service port,
- LP to fill the refrigerant only from the LP service port,
Press ENTER symbol
Edit VACUUM data:
Insert the value of the VACUUM TIME, TIME OF CHECK and press to confirm, to
return back.
NOTE: if selected VACUUM TIME is lower 15 minutes the following popup warning will be
displayed:
Press to continue, or press to go back.
<
DD/MM/YY XX:XX PM
AUTOMATIC / SETTING
PAG1
0 ml
POE H
0 ml
UV H
0 ml
Gas filling
100 g
1
min
min
VACUUM TIME
(min 1 120 max)
DD/MM/YY XX:XX PM
AUTOMATIC / VACUUM
TIME OF CHECK
(min 1 120 max)
1
2
3
4
5
6
7
8
9
.
0
2
DD/MM/YY XX:XX PM AUTOMATIC / VACUUM
The selected vacuum time is lower than 15 minutes
The leak check could not reliable, continue?