Chapter 3: Configuration and Commissioning
50 ModuLaser Modular Aspirating Smoke Detector Installation Manual
To perform an installation test:
1. Select Test from the Main menu, and then select Installation Test.
2. Select the device that you want to test.
The warning indicator flashes slowly to indicate test mode.
3. To end the installation test, press Enter again.
4. Press F2 (Back) twice to return to the Main menu.
Note: An installation test is not terminated by a system reset. The test can only
be terminated from the test menu by unchecking the device in test.
Performing an output test
The output test is used to test outputs OUT1, OUT2, and OUT3 for the selected
module.
To perform an output test:
1. Select Test from the Main menu, and then select Output Test.
2. Select the device that you want to test.
The warning indicator flashes slowly to indicate test mode.
3. Select the outputs that you want to test.
Select ON to start the test and OFF to end the test.
4. Press F2 (Cancel) to end the test.
Outputs will return to their original state when the test ends.
Note: A command module can also perform additional output tests on legacy
devices. See your device documentation for further information.
Performing an input test
The input test is used to test inputs IN1 and IN2 for the selected module.
To perform an input test:
1. Select Test from the Main menu, and then select Input Test.
2. Select the device that you want to test.
The warning indicator flashes slowly to indicate test mode.
3. Change the state of the input and check that the state is updated on the
display (this may take a few seconds).
There are three possible input states; ON, OFF, and Open Circuit.
4. Press F2 (Cancel) to end the test.
Note: Return the input to its default state before ending the test. If not, any
configured input functionality may be activated when the test ends.