EasyManua.ls Logo

EES BSM - 3.9 Technical data

EES BSM
45 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functional description
MSM-USM2G-BA-UK-001 Page 17 of 45
3.9 Technical data
Supply voltage U
Sup
Key
Rated voltage
Voltage range
1
24 V AC/DC
19…37 V DC or 14…26 V AC
2
48 V AC/DC or 60 V DC
37…73 V DC or 26…51 V AC
5
110 V AC/DC or 220 V AC/DC
100…370 V DC or 85…264 V AC
Table 3.3: Supply voltage keys BSM
Signal voltage U
Sig
Key
Rated voltage
[V AC/DC]
Threshold for alarm
Maximum
permitted
voltage
[V AC/DC]
Input current per
input @ rated
voltage
[mA]
Inactive
[V AC/DC]
Active
[V AC/DC]
1
24
11
15
50
2,3
3
48
17
25
75
2,1
60
17
25
75
2,7
4
110
35
50
150
1,6
H
125
35
50
150
1,8
5
220
100
140
260
1,2
Table 3.4: Signal voltage keys BSM
If not otherwise specified the given information for alternating voltage are effective values and refer to
a sinusoidal alternating voltage with a frequency of 50/60 Hz.
Power consumption
Number of
channels
Power consumption [W]
Without integrated repeat
relays
With integrated repeat relays
8
< 4
< 6
16
< 5
< 9
24
< 5
< 13
32
< 6
< 11*
40
< 7
< 19
48
< 8
< 13*
Table 3.5: Power consumption BSM
* The power consumtion of 32- and 48-way annunciators with integrated repeat relays refers to a
maximum number of 2 relay cards (16 relays).
The voltage U
Sig
is valid for signal inputs and function inputs.