06/2016 - Art. Nr. 4200 1041 1103A10
Operation
BT 3xx menu overview
• Menu 1: Setting the
servomotors
• Menu 2: Display of the
setting points of the
servomotors in the
display unit
• Menu 3: Displaying
faults
• Menu 4: Statistical data
• Menu 5: Setting/
modification of
standard configurations
In addition to the function of control and
safety unit, the control and safety unit BT
3xx also modulates the burner output by
controlling the air flap, gas flap, fuel oil
quantity regulation and frequency
converter (optional) in one electronic
circuit.
The electronic circuit controls the
opening of the gas flap and fuel oil flow
regulation proportional to the air flap
along a curve based on 10 setting points
During start up, the setting points are
defined based on the measurement
values of the combustion gas analysis.
This guarantees optimal combustion
over the burner's entire output
modulation range.
A separate burner ignition load can be
defined with the "Ignition position"
setting point .
The limit values of the control range are
defined by the min. output " " and
max. output " " setting points. In
addition, other optional functions, such
as sealing tests, reventilation or waiting
times can be activated.
The combustion control unit is operated
via a display and operating unit. The
parameters for the control and safety
unit are set using the display and 5 keys.
Operating values are shown in real time
on the display.
Pressing the keys gives access to 9
menus:
• Menu 6: Setting/
modification of
configurations for
industrial applications
• Menu 7: Manual mode
• Menu 8: Setting mode
- Menu 8 currently not
available
• Menu 9: Setting the
brightness and contrast of
the display
In these menus, it is
possible to adjust the
standard configurations of
the control unit. These are
pre-set in the factory.
The nearest customer
service department must be
contacted before any on-
site modifications are made.