Commissioning
Adjustment data
Ionisation current measurement
Setting the gas pressure switch
Remove the transparent cover.
Provisionally set to 15 mbar.
Setting the air pressure switch
Remove the transparent cover.
Provisionally set to 1 mbar.
The adjustment values above are guide
values and facilitate commissioning.
The factory settings are in bold set
against a grey background. The final
settings are essential in ensuring that
the burner functions as well as possible.
Ionisation current measurement
To measure the ionisation current,
disconnect connector B10 and connect
a multimeter with a measuring range of
0-100 µA.
The ionisation current must be at least
8 µA. It is also possible to read the
ionisation current on the display.
Ignition load Part load
Full
load Ignition load Part load
Full
load Ignition load
Part
load
Full
load
(°) P0 (°) P9 (°) (°) P0 (°) P9 (°) (Hz) P0 (Hz) P9 (Hz)
169 514 40 8,9 0 0 28,2 17,1 17,1 76,3 50 50 50 8,3
171 677 40 5,3 0 0 41,4 15,6 15,6 76,3 50 50 50 12,6
172 823 40 6 0 0 61,3 14,3 14,3 76,3 50 50 50 17,1
157 511 40 4,6 0 0 28,8 18,1 18,1 76,3 50 50 50 9,8
168 676 40 5,3 0 0 44,6 16,5 16,5 76,3 50 50 50 14,5
171 820 40 6 0 0 61,3 15,5 15,5 76,3 50 50 50 19,0
162 512 40 4,6 0 0 27,0 11,5 11,5 29,0 50 50 50 11,4
160 676 40 5,3 0 0 40,9 11,1 11,1 45,9 50 50 50 12,0
163 822 40 6 0 0 51,4 9,7 9,7 76,3 50 50 50 13,5
163 742 40 5,8 0 0 47,7 14,6 14,6 76,3 50 50 50 14,6
166 862 40 6,2 0 0 54,1 13,9 13,9 76,3 50 50 50 17,4
167 981 40 6,6 0 0 90,0 13,1 13,1 76,3 50 50 50 21,6
167 740 40 5,8 0 0 48,6 15,6 15,6 76,3 50 50 50 16,7
168 869 40 6,2 0 0 61,7 14,9 14,9 76,3 50 50 50 21,0
164 980 40 6,6 0 0 90,0 13,8 13,8 76,3 50 50 50 24,5
163 746 40 5,8 0 0 46,8 7,6 7,6 47,4 50 50 50 13,5
185 861 40 6,2 0 0 58,4 7,6 7,6 45,0 50 50 50 17,1
185 980 40 6,7 0 0 90,0 9,7 9,7 76,3 50 50 50 17,2
VG5.950
M(V) /TC
(PED)
G31
Furnace
pressure
mbar
Part load
Dimen
-
sion
Y
mm
VG5.1200
M(V) /TC
(PED)
G20
G25
G31
Burner
Gas pressure
controller
setting
pBr
mbar
Air flap position Gas throttle position
Full
load
G20
G25
Frequency
(only MV burners)
Burner output
kW
Type of
gas