EasyManuals Logo

elco VG5 M/TC Series User Manual

elco VG5 M/TC Series
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #34 background imageLoading...
Page #34 background image
06/2016 - Art. Nr. 4200 1041 1103A34
Fitting the fan wheel
When changing the motor or the fan
wheel, refer to the positioning diagram
opposite. The internal flange A of the fan
wheel must be aligned with the plate B.
Insert a straight edge between the
blades of the fan wheel and bring A and
B to the same height. Tighten the cone-
point screw on the fan wheel.
Removing the plate
Turn off power supply to the motor (4P
connector).
To do this, unscrew but do not remove
the 7 screws X securing the motor
plate.
Pivot the plate (bayonet system),
extract and remove it carefully
(without damaging the furnace
pressure tap).
Clean the housing, the volute and the
air intake box, and check that there is
no damage.
If necessary, when cleaning, remove
the air recycling unit; to do this,
remove the 4 screws Z and release
the recycling unit.
Clean the ventilation turbine and check
it is not damaged.
Servicing