EasyManua.ls Logo

ELIT EuroMaster AutoEv - Page 85

ELIT EuroMaster AutoEv
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EuroMaster AutoEV
30
RCD / x1/2, x1, x2, x5 (Trip-time)
1x
RCD
10mA
0
----
mS
180
---- mS
AC
General
Uc: --------- V
Ri: ---------
0
1
230
OK
TN-net
229
Figure 6.6.8 RCD / x1/2,x1,x2,x5 screen.
I.
Set the rotary switch to RCD.
II.
Press F1 button to change to x1/2, x1, x2, x5.
III.
Connect the test leads as shown in Figure 6.6.1.
IV.
If there is no problem with the test lead connection, “OK” is displayed as shown in Figure 6.6.8
V.
When “OK” is displayed, press the Test button to perform measurement.
VI.
The symbol being measured is displayed.
VII.
The voltage phase 0 ° is measured first and the Trip time is displayed.
VIII.
When the 0 ° measurement is completed, turn on the RCD switch and measure 180 °.
IX.
When all measurements are completed, the RCD 0 ° and 180 ° Trip time will be displayed on the
screen.
1x
RCD
10mA
0
68
mS
180
43 mS
AC
General
Uc: 10.5 V
Ri: 1000 Ω
0
OK
TN-net
1 230
229
Figure 6.6.9 RCD / x1/2,x1,x2,x5 Measurement completed.

Table of Contents

Related product manuals