79
www.elstat.io
10.29 Saving differential (Sd)
The table below details the saving differential (Sd) parameter
DISPLAY
DESCRIPTION
Defines the compressor cut-in temperature, when added to the saving set point (SSP)
temperature, during the saving mode.
CONSIDERATOINS
If the saving differential (Sd) is set too low, for example less than 2.0°C, the compressor may
cycle on the minimum compressor rest time (rt).
RANGE 0.0 to 9.9°C (0 to 18°F)
GLOBAL DEFAULT
4.0°C (7°F)
ems75sz: 3.0°C (5°F)
10.30 Motion sensor enable (Sn)
The table below details the motion sensor enable (Sn) parameter
DISPLAY
DESCRIPTION Enables the input from the motion sensor.
CONSIDERATOINS Must be disabled if a motion sensor is not fitted.
RANGE 00 (disabled) or 01 (enabled)
GLOBAL DEFAULT 01 (enabled)