81
www.elstat.io
10.33 Saving set point (SSP)
The table below details the saving set point (SSP) parameter
DISPLAY
DESCRIPTION Defines the compressor cut-out temperature during the saving mode.
CONSIDERATOINS Must be set above the set point (SP) plus differential (dIF) temperature.
RANGE
0.0 to 9.9°C (32 to 50°F)
ems75sz: -9.9 to 9.9°C (14 to 50°F)
GLOBAL DEFAULT
all except ems75sz: 7.0°C (45°F)
ems75sz: 3.0°C (37°F)