10.31 Set point (SPC or SPF)
The table below details the set point (SPC or SPF) parameter
DISPLAY
DESCRIPTION
Defines the compressor cut-out temperature during the ready mode. The set point (SP)
temperature is the lowest measured temperature under normal operating conditions.
The set point is displayed as SPC (set point Celsius) or SPF (set point Fahrenheit) depending
on whether the ems controller is set to use Celsius or Fahrenheit.
CONSIDERATOINS Must be above the freeze-up protection (dtt) temperature.
RANGE -9.9 to 9.9°C (14 to 50°F)
GLOBAL DEFAULT
3.0°C (37°F)
ems75sz: -3.0°C (27°F)
10.32 Saving restart period (Sr)
The table below details the saving restart period (Sr) parameter
DISPLAY
DESCRIPTION
Defines the maximum time allocated to reach the set point (SP) temperature from the
saving mode temperature.
CONSIDERATOINS
Set and verified by OEMs through the test protocolto ensure that product temperatures
are within specification when outlets open.
Must be set in multiples of 30 minutes.
RANGE 0 to 240 minutes (in multiples of 30 minutes)
GLOBAL DEFAULT 120 minutes

Table of Contents

Other manuals for Elstat ems25+

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Elstat ems25+ and is the answer not in the manual?

Elstat ems25+ Specifications

General IconGeneral
BrandElstat
Modelems25+
CategoryController
LanguageEnglish

Related product manuals