EasyManua.ls Logo

EMC Connectrix B Series

EMC Connectrix B Series
218 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Facility requirements
149
Specifications
Facility requirements
The facility where the ED-DCX-4S-B is in use must meet the
following requirements to provide for correct operation:
Adequate supply circuit, line fusing, and wire size, as specified
by the electrical rating on the chassis nameplate.
An air flow of at least 350 cubic feet per minute (595 cubic meters
per hour) in the immediate vicinity of the ED-DCX-4S-B.
Electrical interference less than the levels stated in the standards
listed in Table 15 on page 144.
The environmental specifications listed in Table 19 on page 150.
The power specifications listed in Table 20 on page 152.
Furthermore, if the ED-DCX-4S-B will be installed in an EIA rack,
ensure the following:
All equipment installed in the rack has a reliable branch circuit
ground connection, and does not rely on a connection to a branch
circuit, such as a power strip.
The rack is balanced and mechanically secured to provide
stability in the event of an earthquake.
Additional equipment does not exceed the rack’s weight limits.

Table of Contents

Other manuals for EMC Connectrix B Series

Related product manuals