EMC Connectrix B Series v6.2 ED-DCX-4S-B Hardware Reference Manual
Port Side Exhaust Kit Installation Procedure
Ensure that the product fans have access to a total minimum
airflow of 350 cubic ft (9.91 cubic meters) per minute. Do not
block intake vents. Allow for a minimum of 14 in. (35.66 cm)
clearance.
Ensure that the air temperature on the air intake side is less than
104
o
Fahrenheit (40
o
Celsius) during operation.