Mentor MP Short Form Guide 123
Issue Number: 5 www.controltechniques.com
Safety Information Product information
Mechanical
installation
Electrical
installation
Getting started Running the motor
SMARTCARD
operation
Advanced
parameters
Diagnostics
UL listing
EnC2 190 Drive encoder trip: wire break
EnC3 191 Drive encoder trip: overload
EnC9 197
Drive encoder trip: position feedback is selected from a Solutions Module slot
which does not have a speed/position feedback Solutions Module installed
EnC10 198 Drive encoder trip: termination overload
Et 6 External trip from input on terminal 31
FbL 159 No signal from the tachogenerator or encoder
Fbr 160 The polarity of the feedback tachogenerator or encoder is incorrect
FdL 168 No current in the field supply circuit.
FOC 169
Excess current detected in field current feedback. If maximum current
feedback is present when the firing angle is fully phased back then trip
F.O VL 157
Field I
2
t overload
HF01* - Data processing error: CPU address error
HF02* - Data processing error: DMAC address error
HF03* - Data processing error: Illegal instruction
HF04* - Data processing error: Illegal slot instruction
HF05* - Data processing error: Undefined exception
HF06* - Data processing error: Reserved exception
HF07* - Data processing error: Watchdog failure
HF08* - Data processing error: Level 4 crash
HF09* - Data processing error: Heap overflow
HF10* - Data processing error: Router error
HF11* - Data processing error: Access to EEPROM failed
HF12* - Data processing error: Main program stack overflow
HF17* - Data processing error: No Comms from power processor
HF18* - Bucket suppressor capacitor failure
HF19* - Overheat on bucket suppressor or snubber circuits
HF20* - Power stage recognition: identification code error
HF21* - Power processor: Watchdog failure
HF22* - Power processor: Undefined exception
HF23* - Power processor: Level overrun
HF27* - Power circuit: Thermistor 1 fault
HF28* - Power software not compatible with user software
HF29* - User processor: Armature timing error
It.AC 20
I
2
t on drive output current (refer to Pr 4.16)
O.Ld1 26
Digital output overload: total current drawn from digital outputs exceeds 200
mA
O.ht1 21 Drive overheat (thyristor junction) based on thermal model
O.ht2 22 Heatsink over-temperature
O.ht3 27 External discharge resistor over-temperature
O.SPd 7 Motor speed has exceeded the over speed threshold
Pad 34
Keypad has been removed when the drive is receiving the speed reference
from the keypad
PLL Err 174 Phase Lock Loop cannot lock to the auxiliary supply
PS 5 Internal power supply fault
PS.10V 8 10V user power supply current greater than 10 mA
PS.24V 9 24V user power supply current greater than 200 mA
Trip Number Description