74 Mentor MP Short Form Guide
www.controltechniques.com Issue Number: 5
Table 5-3 Menu 40 parameter descriptions
Table 5-4 Menu 41 parameter descriptions
5.8 Saving parameters
When changing a parameter in Menu 0, the new value is saved when pressing the
Mode button to return to parameter view mode from parameter edit mode.
If parameters have been changed in the advanced menus, then the change will not be
saved automatically. A save function must be carried out.
Procedure
1. Enter SAVE in Pr xx.00
2. Either:
• Press the red reset button
• Toggle the reset digital input, or
• Carry out a drive reset through serial communications by setting Pr 10.38 to
100 (ensure that Pr xx.00 returns to 0).
Parameter Range(Ú)
40.00 Parameter 0 0 to 32767
40.01 Language selection
English (0), Custom (1), French (2),
German (3), Spanish (4), Italian (5)
40.02 Software version 999999
40.03 Save to flash Idle (0), Save (1), Restore (2), Default (3)
40.04 LCD contrast 0 to 31
40.05
Drive and attribute database
upload was bypassed
Updated (0), Bypass (1)
40.06 Browsing favourites control Normal (0), Filter (1)
40.07 Keypad security code 0 to 999
40.08
Communication channel
selection
Disable (0), Slot1 (1), Slot2 (2), Slot3 (3),
Slave (4), Direct (5)
40.09 Hardware key code 0 to 999
40.10 Drive node ID (Address) 0 to 255
40.11 Flash ROM memory size 4Mbit (0), 8Mbit (1)
40.19 String database version number 0 to 999999
40.20 Screen saver strings and enable None (0), Default (1), User (2)
40.21 Screen saver interval 0 to 600
40.22 Turbo browse time interval 0 to 200ms
40.23 Connected drive type
Unidrive SP (0),
Commander SK (1), Mentor MP (2),
Affinity (4), Digitax ST (5)
Parameter Range(Ú)
41.00 Parameter 0 0 to 32767
41.01 to
41.50
Browsing filter source F01 to F50 Pr 0.00 to Pr 22.99
41.51 Browsing favourites control Normal (0), Filter (1)