5.9 Restoring parameter defaults
Restoring parameter defaults by this method saves the default values in the drive’s
memory (Pr 11.44 (SE14, 0.35) and Pr 11.30 are not affected by this procedure).
Procedure
1. Ensure the drive is not enabled, i.e. terminal 31 is open or Pr 6.15 is OFF (0)
2. Select Eur or USA in Pr xx.00.
3. Either:
Press the red reset button
Toggle the reset digital input, or
Carry out a drive reset through serial communications by setting Pr 10.38 to
100 (ensure that Pr. xx.00 returns to 0).
5.10 Differences between European and USA defaults
5.11 Displaying parameters with non-default values only
Select dIS.dEf in Pr xx.00, the only parameters that will be visible to the user will be
those containing a non-default value. This function does not require a drive reset to
become active. To deactivate this function, return to Pr xx.00 and enter a value of 0.
Please note that this function can be affected by the access level enabled. You must
refer to section 5.13 Parameter access level and security for more information regarding
access level.
5.12 Displaying destination parameters only
Select dIS.dESt in Pr xx.00, the only parameters that will be visible to the user will be
destination parameters. This function does not require a drive reset to become active.
To deactivate this function, return to Pr xx.00 and enter a value of 0.
Please note that this function can be affected by the access level enabled You must
refer to section 5.13 Parameter access level and security for further information
regarding access levels.
Pr Description Default
2.06 S ramp enable Eur: OFF (0), USA: On (1)
3.51 Tachometer voltage rating (Fb02, 0.72) Eur: 60.00, USA: 50.00
5.09,
21.09
Armature rated voltage
(SE06, 0.27)
480V drive Eur: 440, USA:500
5.28 Field weakening compensation disable Eur: OFF (0), USA On (1)
5.59,
21.08
Back emf set point 480V drive Eur: 440, USA:500
5.65 Economy timeout Eur: OFF (0), USA: On (1)
5.70,
21.24
Rated field current
(SE10, 0.31)
Size 1: Eur: 2.00, USA: 8.00
Size 2A & B Eur: 3.00, USA: 20.00
Size 2C & D Eur: 5.00, USA 20.00
5.73,
21.23
Rated field voltage
(SE11, 0.32)
Eur: 360, USA: 300
5.75 Field voltage mode Eur: OFF (0), USA: On (1)
7.15
Analog input 3 mode
(in01, 0.81)
Eur: th (8), USA: VOLt (6)

Table of Contents

Other manuals for Emerson Mentor MP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Mentor MP and is the answer not in the manual?

Emerson Mentor MP Specifications

General IconGeneral
BrandEmerson
ModelMentor MP
CategoryDC Drives
LanguageEnglish

Related product manuals