* HF (Hardware fault) trip - Return drive to supplier.
th.Err 173 Thyristor missing
thS 25 Motor thermistor short circuit
tunE 18 Autotune stopped before completion
tunE1 11
The position feedback did not change or required speed could not be reached
during the inertia test (refer to Pr 5.12 (SE13, 0.34))
tunE2 12
Position feedback direction incorrect or motor could not be stopped during the
inertia test (refer to Pr 5.12 (SE13, 0.34))
tunE3 13 Field flux has not decayed to zero during autotune
tunE4 14 Back emf detected during autotune
tunE5 15 No field current detected during autotune
tunE6 16
Cannot achieve ¼ rated back emf during autotune. Reset Pr 5.70 (SE10,
0.31) to name plate value and re- autotune motor
tunE7 17 Rotating autotune requested when using estimated speed feedback
UP ACC 98 Onboard PLC program: cannot access Onboard PLC program file on drive
UP div0 90 Onboard PLC program attempted divide by zero
UP OFL 95
Onboard PLC program variables and function block calls using more than the
allowed RAM space (stack overflow)
UP ovr 94 Onboard PLC program attempted out of range parameter write
UP Par 91 Onboard PLC program attempted access to a non-existent parameter
UP ro 92 Onboard PLC program attempted write to a read-only parameter
UP So 93 Onboard PLC program attempted read of a write-only parameter
UP udF 97 Onboard PLC program undefined trip
UP uSEr 96 Onboard PLC program requested a trip
UV 1 Running from external +24V